-1 ERR in GTosPMU_App Streaming Data

description

The -1 ERR in the GTosPMU_App software is an exception raised when the PPS is more than 20 milliseconds late. This error was observed with the GridTrak PMU configured for 50Hz range.

In the next GridTrak release, this exception will be modified to have a configurable value and option to disable (ignore missed PPS).
Closed Apr 17, 2013 at 10:24 PM by ajstadlin
GTosPMU_App 1.0.9.11, source code changeset 84109:

Default Configuraiton for Late PPS set to disable raising the exception in the GTosPMU_App software.
The configuration parameters to enable the Late PPS exception and change its time threshold may be modified in the application's configuration XML file.